Mean Well LAD-240A Security/Fire Alarm PSU with Battery Charger/UPS, 240W, 13.8V 16.4A
Notify me when it's back in stock
Your order will be processed within 24 hours
Overview
LAD-240A is the CH1: 13.8V / CH2: 13.8V output model of this series: rated current CH1: 16.4A / CH2: 1A(Battery Charger), rated power 240.12W, typical efficiency 85.5%.
LAD-240 series is a 240W economical AC/DC low profile security power supply with UPS function. Adopting the input range from 90Vac to 264Vac (115Vac/230Vac selectable by switch) and supports output 13.8V, 27.6V, 41.5V and 55.2Vdc. With high efficiency up to 88% and built-in AC, battery switch for easy maintenance. In addition, LAD-240 series also provide TTL signals for AC OK, battery disconnect, battery reverse polarity (No damage), battery low detection, battery full and discharge, to allow easy integration into security and fire systems directly.
Features
- Built-in battery charger and UPS function
- TTL signals for status detection: AC OK, Battery disconnect, Battery reverse polarity, Battery low, Battery full and Discharge
- Built-in AC and battery circuit ON/OFF switches enhance safetyness during maintenance
- Forced UPS mode for battery maintenance
- Protections: Short circuit / Overload / Over voltage / Over temperature / Battery low voltage / Battery reverse polarity (No damage)
- -20 ~ +60℃ wide operating temperature
- Output voltage adjustable (-20%~+5%) for CH1 by VR
- Suitable for lead acid and lithium-ion batteries
- Design refer to GB17945 system requirement
- 1U low profile (30 mm)
- 3 years warranty
Specifications
OUTPUT
- OUTPUT NUMBER
- CH1 / CH2
- DC VOLTAGE
- CH1: 13.8V / CH2: 13.8V
- RATED CURRENT
- CH1: 16.4A / CH2: 1A(Battery Charger)
- CURRENT RANGE
- CH1: 0 ~ 17.4A / CH2: --------
- RATED POWER
- 240.12W
- RIPPLE & NOISE (max.)Note.2
- CH1: 150mVp-p / CH2: --------
- VOLTAGE ADJ. RANGE
- CH1: 10.8 ~ 14.5V
- VOLTAGE TOLERANCENote.3
- CH1: ±1.5% / CH2: --------
- LINE REGULATION
- CH1: ±0.5% / CH2: --------
- LOAD REGULATION
- CH1: ±1.0% / CH2: --------
- SETUP, RISE TIME
- 2000ms, 50ms/230VAC 2000ms, 50ms/115VAC at full load
- HOLD UP TIME (Typ.)
- 16ms/230VAC 12ms/115VAC at full load
- BATTERY STATIC DISCHARGE CURRENT
- <100μA
INPUT
- VOLTAGE RANGE
- 90 ~ 132VAC / 180 ~ 264VAC by switch 240 ~ 370VDC (Default switch at 230VAC)
- FREQUENCY RANGE
- 47 ~ 63Hz
- EFFICIENCY (Typ.)
- 85.5%
- AC CURRENT (Typ.)
- 4.4A/115VAC 2.4A/230VAC
- INRUSH CURRENT (Typ.)
- COLD START 60A/115VAC 60A/230VAC
- LEAKAGE CURRENT
- <0.5mA / 240VAC
PROTECTION
- OVERLOAD
- CH1:105 ~ 135% CH2:90 ~ 110% Protection type : CH1 OLP, CH2 with battery: The unit will enter to UPS mode when CH1 is around 105%~120%, when total output of CH1 + CH2 reach around 125%~135% output shuts down CH1 OLP, CH2 without battery:Shut down o/p voltage,re-power on to removed CH2 : Constant current limiting; fault condition does not affect CH1 working,recovers automatically after fault condition is removed (External fuse is mandatory in series connection with battery for protection)
- OVER VOLTAGE
- CH1:15.5 ~ 18V Protection type : Shut down o/p voltage, re-power on to removed
- OVER TEMPERATURE
- Protection type : Shut down o/p voltage, re-power on to removed
- BATTERY REVERSE POLARITY
- Protected when reverse polarity , no damage, recovers automatically after fault condition is removed
- BATTERY CUTOFF
- 9.5V±0.5V
FUNCTION
- AC OK
- TTL signal, High / Open : AC Fail ; Low : AC OK ; Ice : max. 30mA@ 50VDC
- BATTERY DISCONNECT/ REVERSE POLARITY
- TTL signal, High / Open : Battery connect/normal ; Low : Battery disconnect/reverse polarity; Ice : max. 30mA@ 50VDC
- BATTERY LOW
- TTL signal, High / Open : Battery normal ; Low : Battery low; Ice : max. 30mA@ 50VDC
- BATTERY FULL
- TTL signal, High / Open : Battery charging ; Low : Battery full ; Ice : max. 30mA@ 50VDC
- DISCHARGE
- TTL signal, High / Open : Charge ; Low : Discharge ; Ice : max. 30mA@ 50VDC
ENVIRONMENT
- WORKING TEMP.
- -20 ~ +60℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 95% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -30 ~ +85℃, 10 ~ 95% RH non-condensing
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃)
- VIBRATION
- 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC
- SAFETY STANDARDS
- UL62368-1, BS EN/EN62368-1, AS/NZS62368.1, EAC TP TC 004 approved; Design refer to GB 17945-2010
- WITHSTAND VOLTAGE
- I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
- ISOLATION RESISTANCE
- I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSION
-
Parameter Standard Test Level Conducted BS EN/EN55032 (CISPR32), EAC TP TC 020 Class A Radiated BS EN/EN55032 (CISPR32), EAC TP TC 020 Class A - EMC IMMUNITY
-
Parameter Standard Test Level ESD BS EN/EN61000-4-2 Level 3, 8KV air; Level 2, 6KV contact; criteria A Radiated BS EN/EN61000-4-3 Level 3, 10V/m; criteria A EFT / Burst BS EN/EN61000-4-4 Level 3, 2KV; criteria A Surge BS EN/EN61000-4-5 Level 3, 1KV/Line-Line ;2KV/Line-FG ;criteria A Conducted BS EN/EN61000-4-6 Level 3, 10V; criteria A Magnetic Field BS EN/EN61000-4-8 Level 4, 30A/m; criteria A
OTHERS
- MTBF
- 1394.9K hrs min. Telcordia SR-332 (Bellcore); 156.7K hrs min. MIL-HDBK-217F (25℃)
- DIMENSION
- 215*115*30mm (L*W*H)
- PACKING
- 0.75Kg; 15pcs/12.25Kg/0.7CUFT
Test conditions and notes6
- 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
- 3. Tolerance : includes set up tolerance, line regulation and load regulation.
- 4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. Radiation testing requires adding 13*26*30NIZN magnetic loops or buckles to the battery output wire. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
- 5. This power supply does not meet the harmonic current requirements outlined by BS EN/EN61000-3-2. Please do not use this power supply under the following conditions: a) the end-devices is used within the European Union, and b) the end-devices is connected to public mains supply with 220Vac or greater rated nominal voltage, and c) the power supply is: - installed in end-devices with average or continuous input power greater than 75W, or - belong to part of a lighting system Exception: Power supplies used within the following end-devices do not need to fulfill BS EN/EN61000-3-2 a) professional equipment with a total rated input power greater than 1000W; b) symmetrically controlled heating elements with a rated power less than or equal to 200W
- 6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
Technical drawings
Typical applications
- Fire emergency and evacuation system
- Public safety battery back-up
- Security system
- Uninterruptible DC-UPS system
- Central monitoring system
- Industrial automation
Downloads
Datasheet1
FAQ
What is the Mean Well LAD-240A designed for?
The LAD-240A is a 240W security and fire alarm power supply with a built-in battery charger and UPS function. It is intended for systems that need a regulated 13.8VDC output plus battery-backed continuity during AC power loss.
What output does the LAD-240A provide?
This model is rated for 13.8VDC output and 16.4A rated current on CH1, with a total power rating of 240W and a 1A battery charger output on CH2. The CH1 output voltage is also adjustable within the 10.8 to 14.5V range.
Does the LAD-240A support backup battery operation?
Yes. The LAD-240A includes a built-in battery charger and UPS function, so it can support battery-backed operation for security and fire alarm systems. It also includes a forced start UPS mode, selected by shorting CN2 pins 7 and 8.
What protection and monitoring features are included in the LAD-240A?
The unit includes protection for overload, over voltage, over temperature, battery low voltage (cutoff at 9.5V±0.5V), and battery reverse polarity with no damage. It also provides TTL status signals for AC OK, battery disconnect, battery reverse polarity, battery low, battery full, and discharge status detection.
Can the LAD-240A be used in demanding indoor equipment environments?
It is rated for an operating temperature range of -20 to +60 degrees C, with output derating at higher temperatures per the derating curve, and has a low-profile 30mm-high case. That makes it suitable for compact indoor security or fire system enclosures where space and operating conditions matter.
What compliance and standards information is available for the LAD-240A?
The LAD-240A is listed with UL62368-1, BS EN/EN62368-1, AS/NZS62368.1, and EAC TP TC 004 approvals. Its design also refers to GB 17945-2010, and EMC coverage includes EN55032 Class A and multiple EN61000 immunity standards.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other LAD Series Models
19 other modelsPlease log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.