Over 15 years experience of providing support of MEAN WELL Power Supplies
Mean Well LAD-600D Security/Fire Alarm PSU with Battery Charger/UPS, 600W, 55.2V, TTL Signal 7.87A
Notify me when it's back in stock
Your order will be processed within 24 hours
Overview
LAD-600D is the model of this series: rated power 600.02W, typical efficiency 91%. Type Blank: TTL signal only.
LAD-600 series is a 600W economical AC/DC low profile security power supply with UPS function. Adopting the input range from 90Vac to 264Vac (115Vac/230Vac selectable by switch) and supports output 27.6V, 41.5V and 55.2Vdc. With high efficiency up to 91% and built-in AC, battery switch for easy maintenance. In addition, LAD-600 series not only provide TTL signals for AC OK, battery disconnect, battery reverse polarity (No damage), battery low detection, battery full and discharge, but also possess UART version so the users can monitor and control the status of the units, that enhance easy way for integration into security and fire systems directly.
Features
- Built-in battery charger UPS function
- TTL signals for status detection: AC OK, Battery disconnect, Battery reverse polarity, Battery low, Battery full and Discharge (Blank version only)
- UART Communication (U version only)
- Built-in buzzer alarm (U version only)
- Built-in AC and battery circuit ON/OFF switches enhance safetyness during maintenance
- Forced UPS mode for battery maintenance
- Protections: Short circuit / Overload / Over voltage / Over temperature / Battery low voltage / Battery reverse polarity (No damage)
- -20 ~ +60℃ wide operating temperature
- Output voltage adjustable (-20%~+5%) for CH1 by VR
- Suitable for lead acid and lithium-ion batteries
- Design refer to GB17945/GB4717(U version only) system requirement
- 1U low profile
- 3 years warranty
Model encoding
| Type | Function |
|---|---|
| Blank (this model) | TTL signal only |
| U | UART Communication only |
Specifications
OUTPUT
- OUTPUT NUMBER
- CH1, CH2
- DC VOLTAGE (CH1)
- 55.2V
- DC VOLTAGE (CH2)
- 55.2V
- RATED CURRENT (CH1)
- 7.87A
- RATED CURRENT (CH2)
- 3A(Battery Charger)
- CURRENT RANGE (CH1)
- 0 ~ 10.87A
- CURRENT RANGE (CH2)
- --------
- RATED POWER
- 600.02W
- RIPPLE & NOISE (max.) (CH1)Note.2
- 360mVp-p
- RIPPLE & NOISE (max.) (CH2)Note.2
- --------
- VOLTAGE ADJ. RANGE
- Ch1: 43.5 ~ 58V
- VOLTAGE TOLERANCE (CH1)Note.3
- ±1.0%
- VOLTAGE TOLERANCE (CH2)Note.3
- --------
- LINE REGULATION (CH1)
- ±0.5%
- LINE REGULATION (CH2)
- --------
- LOAD REGULATION (CH1)
- ±0.5%
- LOAD REGULATION (CH2)
- --------
- SETUP, RISE TIME
- 2000ms, 50ms/230VAC 2000ms, 50ms/115VAC at full load
- HOLD UP TIME (Typ.)
- 16ms/230VAC 12ms/115VAC at full load
- BATTERY STATIC DISCHARGE CURRENT
- <100μA
INPUT
- VOLTAGE RANGE
- 90 ~ 132VAC / 180 ~ 264VAC by switch 240 ~ 370VDC (Default switch at 230VAC)
- FREQUENCY RANGE
- 47 ~ 63Hz
- EFFICIENCY (Typ.)
- 91%
- AC CURRENT (Typ.)
- 12A/115VAC 7.5A/230VAC
- INRUSH CURRENT (Typ.)
- COLD START 35A/115VAC 60A/230VAC
- LEAKAGE CURRENT
- <0.5mA Peak / 240VAC
PROTECTION
- OVERLOADNote.4
- CH1:105 ~ 135% CH2:90 ~ 110% Protection type : CH1 OLP, CH2 with battery: The unit will enter to UPS mode when CH1 is around 105%~120%, when total output of CH1 + CH2 reach around 125%~135% output shuts down CH1 OLP, CH2 without battery:Shut down o/p voltage,re-power on to removed CH2 : Constant current limiting; fault condition does not affect CH1 working,recovers automatically after fault condition is removed (External fuse is mandatory in series connection with battery for protection)
- OVER VOLTAGENote.4
- CH1:59 ~ 69V Protection type : Shut down o/p voltage, re-power on to removed
- OVER TEMPERATURENote.4
- Protection type : Shut down o/p voltage, re-power on to removed
- BATTERY REVERSE POLARITY
- Protected when reverse polarity , no damage, recovers automatically after fault condition is removed
- BATTERY CUTOFF
- 43V±0.5V
FUNCTION
- AC OK
- TTL signal, High / Open : AC Fail ; Low : AC OK ; Ice : max. 30mA@ 50VDC
- BATTERY DISCONNECT/ REVERSE POLARITY
- TTL signal, High / Open : Battery connect/normal ; Low : Battery disconnect/reverse polarity; Ice : max. 30mA@ 50VDC
- BATTERY LOW
- TTL signal, High / Open : Battery normal ; Low : Battery low; Ice : max. 30mA@ 50VDC
- BATTERY FULL
- TTL signal, High / Open : Battery charging ; Low : Battery full ; Ice : max. 30mA@ 50VDC
- DISCHARGE
- TTL signal, High / Open : Charge ; Low : Discharge ; Ice : max. 30mA@ 50VDC
ENVIRONMENT
- WORKING TEMP.
- -20 ~ +60℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 95% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -30 ~ +85℃, 10 ~ 95% RH non-condensing
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃)
- VIBRATION
- 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC
- SAFETY STANDARDS
- UL62368-1, BS EN/EN62368-1,AS/NZS62368.1, EAC TP TC 004 approved; Design refer to GB 17945-2010
- WITHSTAND VOLTAGE
- I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
- ISOLATION RESISTANCE
- I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSION
-
Parameter Standard Test Level Conducted BS EN/EN55032 (CISPR32), EAC TP TC 020 Class A Radiated BS EN/EN55032 (CISPR32), EAC TP TC 020 Class A - EMC IMMUNITY
-
Parameter Standard Test Level ESD BS EN/EN61000-4-2 Level 3, 8KV air; Level 2, 6KV contact; criteria A Radiated BS EN/EN61000-4-3 Level 3, 10V/m; criteria A EFT / Burst BS EN/EN61000-4-4 Level 3, 2KV; criteria A Surge BS EN/EN61000-4-5 Level 3, 1KV/Line-Line; 2KV/Line-FG ;criteria A Conducted BS EN/EN61000-4-6 Level 3, 10V; criteria A Magnetic Field BS EN/EN61000-4-8 Level 4, 30A/m; criteria A
OTHERS
- MTBF
- 1154.4K hrs min. Telcordia SR-332 (Bellcore); 169.9K hrs min. MIL-HDBK-217F (25℃)
- DIMENSION
- 225*124*41mm (L*W*H)
- PACKING
- 1.02Kg; 12pcs/13.5Kg/0.78CUFT
Test conditions and notes7
- 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
- 3. Tolerance : includes set up tolerance, line regulation and load regulation.
- 4. Once the protection is triggered, the input voltage needs to be disconnected, and the cold machine will wait for 3 minutes before restarting.
- 5. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. All the radiation tests require an additional 20*30*13 NIZN magnetic clasp or magnetic ring to the battery output line. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
- 6. This power supply does not meet the harmonic current requirements outlined by BS EN/EN61000-3-2. Please do not use this power supply under the following conditions: a) the end-devices is used within the European Union, and b) the end-devices is connected to public mains supply with 220Vac or greater rated nominal voltage, and c) the power supply is: - installed in end-devices with average or continuous input power greater than 75W, or - belong to part of a lighting system Exception: Power supplies used within the following end-devices do not need to fulfill BS EN/EN61000-3-2 a) professional equipment with a total rated input power greater than 1000W; b) symmetrically controlled heating elements with a rated power less than or equal to 200W
- 7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
Technical drawings
Typical applications
- Fire emergency and evacuation system
- Public safety battery back-up
- Security system
- Uninterruptible DC-UPS system
- Central monitoring system
- Industrial automation
Downloads
Datasheet1
FAQ
What is the Mean Well LAD-600D designed for?
The LAD-600D is a 600W security and fire alarm power supply with a built-in battery charger and UPS function. It is intended for systems that need continuous DC output with battery backup support and status monitoring.
What are the main output specifications of the LAD-600D?
This model provides a 55.2V DC output and is rated for 600W total power. Its rated output current is 7.87A, and the CH1 output voltage can be adjusted within the specified range of 43.5V to 58V.
Does the LAD-600D support battery backup operation?
Yes. The LAD-600D includes a built-in battery charger and UPS function, so it is designed to support battery-backed operation. It also includes a forced UPS mode for battery maintenance.
What battery types is the LAD-600D compatible with?
Mean Well's sheet lists selectable lead-acid and Li-ion charging curves only for the UART version (LAD-600DU). For the LAD-600D itself, the sheet specifies a 3A battery charger output on CH2 with a battery cutoff at 43V±0.5V.
What status signals are available on the LAD-600D?
The LAD-600D provides TTL signals for system status detection. These cover AC OK, battery disconnect, battery reverse polarity, battery low, battery full, and discharge status.
Can the LAD-600D be used in demanding temperature conditions?
Yes. This power supply is rated for operation from -20°C to +60°C, which supports use in a wide range of indoor equipment environments. Buyers should still confirm the overall enclosure and system design are suitable for the intended ambient conditions.
What protection features are included in the LAD-600D?
This model includes protection for overload, over voltage, over temperature, battery cutoff at 43V±0.5V, and battery reverse polarity. Mean Well also notes that reverse battery polarity causes no damage to the unit.
How does the LAD-600D differ from a standard AC-DC power supply?
Unlike a basic AC-DC supply, the LAD-600D combines regulated DC output with battery charging, UPS functionality, and TTL status signaling in one unit. That makes it better suited to monitored security and fire alarm systems that need backup power capability.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other LAD Series Models
19 other modelsPlease log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.